FAQ-Battery Over Temperature alarm generate, what should be done

Publication Date:  2014-10-30 Views:  552 Downloads:  0
Issue Description
Battery Over Temperature alarm generate, what should be done?
Solution
Possible Causes:
1) The battery overtemperature alarm threshold is not set properly on the SMU.
2) The battery temperature controlling system is faulty.
3) The battery temperature sensor is faulty.

Measures:

1) Check whether the battery overtemperature alarm threshold (50°C by default) is properly set. If no, adjust it to a proper value.

2) Check whether the battery temperature controlling system is faulty. If yes, rectify the fault. The alarm is cleared when the battery temperature falls within the allowed range.

3) Check whether the battery temperature sensor is faulty. If yes, replace the temperature sensor.