Publication Date:  2014-10-30 Views:  458 Downloads:  0
Issue Description
Battery Over Curr alarm generate, what should be done?
Solution
Possible Causes:
1) The rectifier communication is interrupted.
2) Poor contact of the SMU.
3) The SMU is faulty.

Measures:

1) Check whether an alarm is generated for rectifier communication interruption. If yes, remove the rectifier and reinstall it to check whether the alarm is cleared. If the alarm still exists, replace the rectifier.

2) Remove the SMU and reinstall it to check whether the alarm is cleared. If the alarm still exists, replace the SMU.