FAQ-Battery Loop Trip alarm generate, what should be done

Publication Date:  2014-10-30 Views:  514 Downloads:  0
Issue Description
Battery Loop Trip alarm generate, what should be done?
Solution
Possible Causes:
1) The battery circuit breaker trips or battery fuse detection cable is disconnected.
2) The battery circuit breaker trips or battery fuse is blown.
3) The contactor is faulty.

Measures:

1) Check whether the battery circuit breaker trips or battery fuse detection cable is disconnected. If yes, reconnect the cable.

2) Check whether the battery circuit breaker trips or battery fuse is blown. If yes, rectify the battery loop fault and then switch on the circuit breaker or replace the fuse.

3) Manually switch on or switch off the battery contactor and check the battery current changes accordingly. If no, replace the contactor.

END