How to use ANT-20 to test 7 days holdover item

Publication Date:  2012-07-24 Views:  64 Downloads:  0
Issue Description
The ANT-20 can supports BITS 7 days holdover test item, but for the ANT-20 default standard test template, it can not supports the test.
      
      
Alarm Information
Use all the default standard template, the test result will be fail;
      
Handling Process
1.After check with R&D, they mention it should change the template of 7 days holdover, here attached this template.
2.In the ANT-20(C:\ANT-20\mask) are the template folder; Or you can in the MTIE analyzer view, that select the template, then you can choose the "browse", then you will know where the 
template folder is;
3.Copy the new template into this folder then you can select the correct one;
      
      
Root Cause
Because all the default standard template are not suit for the G.812 7 days holdover test item;
      
      
Suggestions
If you want to use ANT-20 test the 7 days holdover item, it should change the template.
      