The power module-parameter command is failed because the batteries charge mode is wrong

Publication Date:  2012-07-24 Views:  34 Downloads:  0
Issue Description
When we execute "power module-parameter" command to change the POWER4845 battery number in CLI, it is failed. The prompt information is "Failure: Not remote control state,charge mode is automatic".
Alarm Information
Null
Handling Process
The correct method to solve this problem is like following:
1- please execute command "display power system parameter " to check following item: charge control state/battery number/power module number;
2- if battery number=0, please change it to nonzero;
3- if power module number = 0, please execute command "power module-num " to change it to nonzero;
4- if charge control state = automatic, please execute command "power charge mode " to change it to equalizing/floating;
5- then you can execute "power module-parameter" successfully.
Root Cause
This is because the charge control state is set to automatic. But when we execute the power charge mode to change the charge control state to equalizing/floating, it is also failed.
Suggestions
Null

END