Alarm beeper problem in BITS V5

Publication Date:  2012-07-25 Views:  51 Downloads:  0
Issue Description
When i power ON the BITS at first time then beeper alarm beeps for once.
When i switchoff one power supply then alarm beeper does not beep.
When I pullout standby SOMU board then alarm beeper does not beeps.
When I pullout active SOMU board then alarm beeper beeps for once.
In all three case only alarm LED glows.
Alarm Information
Only alarm LED glows for the Major and Minor alarm but alarm beeper doesn't beeps.
Handling Process
I changed the position of the SOMU boards but problem remains same.
I configure the BITS again but problem has not resolved. 
Then  I go to the alarm manager of SynlockV3 Program. 
Then select the alarm sound option and click on alarm button in BITS Sound control row. Then alarm beeper starts beeping.
Root Cause
In fresh BITS V5 the beeper alarm is not configure.  Thats why alarm beeper does not beeps.
Suggestions
So my suggestion is we can use this troubleshooting as a part of configuration of BITS V5. By doing this beeper will beep properly and it will be easy for customer to monitor the equipment. This troubleshooting can be used for BOTS V3 and BITS V2 also.

END