No alarm generated after swtich off the power swtich of PWX Board because PWX wrongly configured

Publication Date:  2012-07-25 Views:  35 Downloads:  0
Issue Description
No alarm generated when PWX power swtich is off  because  wrong configure of the PWX
UA5000V100R019C00
UA5000(config)#display board 0
  -------------------------------------------------------------------------
  SlotID  BoardName  Status         Sub0     Sub1         Online/Offline
  -------------------------------------------------------------------------
  0       PWX2    Normal                          
  1       PWX2   Normal                          
  2                     
  3                     
  4       H601PVMD   Active_normal  H602ETCA         
  5       H601PVMD   Standby_normal H602ETCA         
  6                     
  7                     
  8                     
  9                     
  10                    
  11      A64        Normal                          
  12      A64        Normal                          
  13      A64        Normal                          
  14      A64        Normal                          
  15      A64        Normal                          
  16                    
  17                    
  18      A64        Normal                          
  19      A64        Normal                          
  20      A64        Normal                          
  21      A64        Normal                          
  22      A64        Normal                          
  23      A64        Normal                          
  24      A64        Normal                          
  25      A64        Normal                          
  26                    
  27                    
  28                    
  29                    
  30                    
  31                    
  32                    
  33                    
  34                    
  35                    
  -------------------------------------------------------------------------
Alarm Information
! FAULT MAJOR 2011-03-14 17:58:07+08:00 ALARM NAME :The +5V of PWXB fault
  PARAMETERS :FrameID: 0, SlotID: 1, Name: H602PWX
! FAULT MAJOR 2011-03-14 17:58:07+08:00 ALARM NAME :The -5V of PWXB fault
  PARAMETERS :FrameID: 0, SlotID: 1, Name: H602PWX
Handling Process
1- Reset the PWX board 
2- Deleted PWX board and re-add it but still the alarm did not appeared 
3-  check another PWX board .
4- PWX board is deleted and added correctly as H602PWX  not PWX2
 so after  the PWX board power swtich is off so  the alarm is generated  .
PWX part :03020NWE  model:H60D00PWX601
UA5000(config)#
! RECOVERY CLEARED 2011-03-14 17:58:50+08:00
  ALARM NAME :The +5V of PWXB recovery
  PARAMETERS :FrameID: 0, SlotID: 1, Name: H602PWX
UA5000(config)#
! RECOVERY CLEARED 2011-03-14 17:58:50+08:00
  ALARM NAME :The -5V of PWXB recovery
  PARAMETERS :FrameID: 0, SlotID: 1, Name: H602PWX
UA5000(config)#
! RECOVERY CLEARED 2011-03-14 17:58:51+08:00
  ALARM NAME :The ringing current of PWXB recovery
  PARAMETERS :FrameID: 0, SlotID: 1, Name: H602PWX
Root Cause
1- Reset the PWX board 
2- Deleted PWX board and re-add it but still the alarm did not appeared 
3-  check another PWX board .
Suggestions
Null