No relevant resource is found in the selected language.

This site uses cookies. By continuing to browse the site you are agreeing to our use of cookies. Read our privacy policy>

Reminder

To have a better experience, please upgrade your IE browser.

upgrade

FAQ-How to monitor the power using the VESC of the MA561x

Publication Date:  2012-07-25 Views:  153 Downloads:  0
Issue Description
Q:
How to monitor the power using the VESC of the MA561x? VESC is the virtual ESC of the MA561x, which can be connected to a digital sensor (for monitoring digital parameters only). VESC supports three Boolean values, among which one is reserved. 
Alarm Information
Null
Handling Process
A:
1. The ALARM port (RJ45 port) on the front panel of the control board is connected to a network cable, which must be a straight-through cable whose wire sequence is orange, blue, green, and brown. 
2. The wire sequence of the other end of the network cable is as follows: 
Green: 0-door status sensor alarm
Blue: 1-lightning arrester alarm
Brown: 2-MDF alarm
The blue, green, and brown twisted pairs can be connected to the power monitoring system to monitor the power by digital parameters. 
3. Connect the twisted pairs (brown for example) to the power monitoring system, check whether ESC digital parameter alarm is generated, and query the valid high level and low level of digital parameters. 
huawei(config-if-h831vesc-0)#display esc environment info                        
EMU ID: 0                             ESC environment state
  ---------------------------Digital environment info-------------------------
  ID Name                State  Value |ID Name                State  Value
  0  Door                Normal 1     |1  Arrester            Normal 1
  2  Wiring              Alarm  1
  ----------------------------------------------------------------------------
If an alarm is generated, the high level and low level of digital parameters are incorrectly defined. In this case, correct them to clear the alarm. The low level is presented by 0 and high level is presented by 1. 
huawei(config-if-h831vesc-0)#esc digital
{ digitalid<U><0,3> }:2
{ available-level<K> }:available-level
{ available-level<E><low-level,high-level> }:low-level
  Command:
          esc digital 2 available-level low-level
After modification, the alarm is cleared. That is, VESC is used for power monitoring. 
Root Cause
Null
Suggestions
Both versions R306 and R307 support power monitoring by VESC. Also, VESC can be used for monitoring other digital parameters. 
The alarm name defined on the equipment cannot be modified. If dry contact is used for monitoring other environment parameters, such as DC current, you need to define the corresponding alarm on the NMS. 

END