Publication Date:  2014-05-28 Views:  121 Downloads:  0
Issue Description
UPS system will sent notification each two months for new installed UPS.This notification inform the administrator to make a new  Battery maintenance . Faulty ID :0036-01.
Alarm Information
ID:0036-01
Handling Process
After click “main” in the screen and the notification disappeared. 
Root Cause
Because the default setting of "test notificaition" in the UPS is 60 Days , After the installation of UPS , 60 days later  , administrator will get the alarm in the system.
Suggestions
If administrator wants to disable the notification , the administrator could disable the setting as the picture.

END