New RH2288H V3 Server's Shows FAN Faulty Alarms

Publication Date:  2017-12-03 Views:  85 Downloads:  0
Issue Description

4 newly purchased RH2288H V3 Server's shows FAN faulty alarms.

 

Server Details:- Description=Function Module,RH2288H V3,BC4M20HGSA,RH2288H V3 (12HDD EXP Chassis) H22H-03 For oversea(except Japan)

 

SN of 4 Servers :-

2102311GHL10H600001X
2102311GHL10H600001X
2102311GHL10H600001X
2102311GHL10H600001X

Alarm Information

Here is the alarm details from all 4 servers.

 

Server 1:-

Server 2:-

Server 3:-

Server 4:-

 

Handling Process

Collect all 4 servers iBMC logs as below guide and request BOQ for the purchase.

Root Cause

As per BOQ, the CPU which customer purchased is E5-2650 v4 which Power consumption will be 105W.

 

 

 

From the BMC logs, the CPU type installed on 4 servers are E5-2667 v4, Power comsumption:135W.

Above can be checked in iBMC logs. Path :- \dump_info\AppDump\CpuMem\cpu_info

 

Also, as per BOQ the shipping FAN BOM is 02310YKN which is 8056 Fan module.

 

Solution

When server installed with 2 Units CPU which power consumption is more than 135W , the fans modules must be 4 Units of 8056 Plus (BOM:02310YKP), otherwise BMC will report Fan failure alarm when boot up.

 

If customer wants to change the CPU type to E5-2667 v4, then they should choose the FAN modules 8056 Plus (BOM:02310YKP).

Suggestions

Check all the component compatibility when customize a server specification. Different type/model of CPU required different type of FAN, Power Modules and other components.

END