/During the comissioning the air conditioner shows alarms and stop to work

Publication Date:  2017-12-15 Views:  377 Downloads:  0
Issue Description
During the installation, supplier maked a mistake os power and signal cable conection betweeen indoor to outdoor machines. The connect the cable from indoor A to outdoor B and Indoor B to outdoor A, so when all machines power on both indoor and outdoor machines, can't find the mistake because the airconditioner can work for some time. After fix cable connection the problem was solved.


Alarm Information

062
Comp HP switch locked and Comp discharge HP locked

Handling Process
Current status: Get feedback from FSE of the next informationFrom your picture I can see 2 active alarms a009 Comp HP switchlocked a058 Comp discharge HP locked Follow the suggestions in order to troubleshoot the alarms. 1. The outdoor unit input power has an openphase, incorrect phase sequence, or is unavailable. Please checkif the OUTDOOR UNIT has voltage, Measure the voltage L1-L2, L2-L3, L1-L3. Ifone phase is lost, check the connections upstream and fix the problem. If the voltageis normal verify the Phase sequence. 2. Signal cables to the outdoor unit are notproperly connected. Verify the signal cables base in the current installation,follow the link in order to check the quick installation guide. http://support.huawei.com/enterprise/en/doc/DOC1000104407?idPath=9452479%7C9475817%7C21110992%7C19891672 3. The condenser fins are blocked. Please confirmif the space is enough where the outdoor unit is installed and there is notobstacles in the condenser coil. (share some pictures of the outdoor unit) 4. The outdoor fan driver or fan is faulty. Please confirm if the Fans installed in Outdoorunit are working normally. 5. Cables to the high pressure switch are notproperly connected. Check the high-pressure switch status. 6. The high pressure switch is faulty. 7. The EEV (Electronic expansion valve) isfaulty. 8. The refrigerant is overfilled. How many Kg ofrefrigerant did you add in the system per each unit? 9. The outdoor unit is installed improperly. After review all the parameters, please clear the alarmsmanually and start the Unit. When the device is running, go to check if the outside unitis running and please take a picture of all the running parameters ofcompressor. Next plan: confirm with FSE the steps above. Remote support. Next update: 11/12/2017
Power and Signal cables was exchange. After fix problem solved.
Root Cause
Wrong connection of Power and signal cables (Indoor to Outdoor machines)
Solution
The cables communication RS 485 were exchanged.
Suggestions

Make the connection carefully in order to avoid this kind of mistake.

END