Power Monitoring Card in the DC PDF Fails to Be Registered Due to the Incorrect Configuration

Publication Date:  2013-09-03 Views:  55 Downloads:  0
Issue Description
The display device command output shows that slot 24 is blank, indicating that the power monitoring card is not registered. In normal cases, DPR is displayed for slot 24.

The RUN indicator of the power monitoring card in the DC power distribution frame (PDF) blinks fast.
Handling Process
1. Remove and then insert the power monitoring card. The RUN indicator still blinks.
2. Run the display device command. The command output shows that no power monitoring card is registered. The IP address of the power monitoring card may be incorrectly configured.
3. Remove the power monitoring card and set its IP address by configuring the dual in-line package switch (DIP switch). Insert the power monitoring card into slot 24 again. The power monitoring card is registered successfully.
For details about how to set the IP address of the power monitoring card by configuring its DIP switch, see the attachment.
Root Cause
The DIP switch on the power monitoring card is incorrectly configured.
Solution
Correctly configure the DIP switch according to the attachment.
Suggestions
Correctly configure the DIP switch according to the attachment.

END