FAQ-AC Over Voltage alarm generate, what should be done

Publication Date:  2014-10-30 Views:  335 Downloads:  0
Issue Description
AC Over Voltage alarm generate, what should be done?
Solution
Possible Causes:
1) The AC overvoltage alarm threshold is not set properly on the SMU.
2) The power grid is faulty.

Measures:

1) Check whether the AC overvoltage alarm threshold is properly set. If no, adjust it to a proper value.

2) Check whether the AC input voltage exceeds the AC overvoltage alarm threshold (280 V AC by default). If yes, handle the AC input fault.

END