FAQ-What can I do if the circuit breaker automatically trips upon a storage system power module switchover

Publication Date:  2015-07-24 Views:  149 Downloads:  0
Issue Description
What can I do if the circuit breaker automatically trips upon a storage system power module switchover?

Solution
The tripping is caused by the insufficient capacity of the circuit breaker.

To eliminate storage system anomalies caused by a single power module failure, the circuit breaker of the external power supply must meet the following specifications:
  • 6 A (AC power)
  • 20 A (DC power)

END