问题描述

S7706交换机所在机房环境良好,但是设备的风扇运行速度达100%

------------------------------------------------------------------------------
           FAN1   [1-2]     YES     YES      29%(1470)    AUTO
                     1                           1500
                     2                           1440
           FAN2   [1-2]     YES     YES      100%(4395)   AUTO   //运行速度100%
                     1                           4380
                     2                           4410

处理过程

1、确认风扇运行阈值配置在正常范围之内

display fan  speed-adjust threshold minus
-----------------------------------------------------------
 Slot     Default Range  Current Range  Speed Rate Adjusted
-----------------------------------------------------------
  2          56 - 60         56 - 60        30%-100%
  3          56 - 60         56 - 60        30%-100%
  7          52 - 56         52 - 56        30%-100%

2、确认设备温度在正常范围之内

display temperature all
-----------------------------------------------------------
 Slot Card SDR No.  Status   Upper  Lower  Temperature.(C)
-----------------------------------------------------------
  2    -    1       normal   67.00  0.00   27.00
  3    -    1       normal   67.00  0.00   28.00
  7    -    1       normal   65.00  0.00   32.00

3、通过查看光模块温度达到127度,信息如下:

XGigabitEthernet3/0/0 transceiver information:
-------------------------------------------------------------
Alarm information:
  Temp high
  Voltage high
-------------------------------------------------------------
Diagnostic information:
  Temperature(°C)                      :127
  Voltage(V)                            :5.08
  Bias Current(mA)                      :28.37
  Bias High Threshold(mA)               :100.00
  Bias Low  Threshold(mA)               :10.00
  Current Rx Power(dBM)                 :2.13   //收光太高,超过收光阈值,导致光模块温度过高
  Default Rx Power High Threshold(dBM)  :1.00
  Default Rx Power Low  Threshold(dBM)  :-16.40
  Current Tx Power(dBM)                 :-4.38
  Default Tx Power High Threshold(dBM)  :1.00
  Default Tx Power Low  Threshold(dBM)  :-8.00

根因

1、XGE3/0/0接口光模块接口温度太高,导致风扇自动调速。

2、据了解:互联设备跨机房中间存在传输设备,本侧传输设备发光过高导致S7700交换机接口XGE3/0/0收光过高。

解决方案
在接口XGE3/0/0及其他收光过高接口增加-5dBm或-7dBm光衰,经观察设备风扇运行速度降至正常工作速率。