FAQ-Single Rectifier Fault alarm generate, what should be done

Publication Date:  2014-10-30 Views:  449 Downloads:  0
Issue Description
Single Rectifier Fault alarm generate, what should be done?
Solution
Possible Causes:
1) The subrack or slot connector is faulty.
2) The rectifier is faulty.
3) The monitoring unit is faulty.

Measures:

1) Remove the rectifier and check whether the slot connector is damaged or deformed. If yes, repair or replace the subrack or slot connector.

2) If the alarm persists after the rectifier is reinstalled, replace the rectifier.

3) If the alarm persists after the monitoring unit is restarted, replace the monitoring unit.