FAQ- Water accumulates on the floor near precision air conditioners. What should be done

Publication Date:  2014-10-29 Views:  114 Downloads:  0
Issue Description
 Water accumulates on the floor near precision air conditioners. What should be done?
Solution
Possible Causes:
1) Precision air conditioners blow moist air.
2) Precision air conditioners are not leveled.
3) Condensate water pipes of the precision air conditioners are blocked.
4) The drainage loop leaks.
5) The insulation layer on the pipes is damaged.
6) The charging pipe of the humidifier leaks.

Procedure:

Step 1 Check whether the precision air conditioners blow moist air.

Y: If the precision air conditioners blow moist air, troubleshoot the air conditioners by referring to 8 Precision Air Conditioners Blow Moist Air and check whether the fault persists.
If the fault is rectified, troubleshooting is complete.
If the fault persists, go to Step 2.
N: If the air conditioners do not blow moist air, go to Step 2.

Step 2 Check whether precision air conditioners are leveled.

Y: If the precision air conditioners are leveled, go to Step 3.
N: If the precision air conditioners are not leveled, level them by referring to the air conditioner installation guide and check whether the fault persists.
If the fault is rectified, troubleshooting is complete.
If the fault persists, go to Step 3.

Step 3 Check whether the condensate water pipes are blocked.

Y: If the condensate water pipe is blocked, clean the condensate water pipe and check whether the fault persists.
If the fault is rectified, troubleshooting is complete.
If the fault persists, go to Step 4.
N: If the condensate water pipe is not blocked, go to Step 4.

Step 4 Check whether the drainage loop leaks.

Y: If the drainage loop leaks, replace the drainpipe and check whether the fault persists.
If the fault is rectified, troubleshooting is complete.
If the fault persists, go to Step 5.
N: If the drainage loop does not leak, go to Step 5.

Step 5 Check whether the insulation layer on the pipes are damaged.

Y: If the insulation layer is intact, go to Step 6.
N: If the insulation layer is damaged, wrap insulation cotton again, and check whether the fault persists.
If the fault is rectified, troubleshooting is complete.
If the fault persists, go to Step 6.

Step 6 Check whether the charging pipe of the humidifier leaks.

Y: If the charging pipe leaks, replace it and check whether the fault persists.
If the fault is rectified, troubleshooting is complete.
If the fault persists, contact Huawei technical support.
N: If the charging pipe does not leak, contact Huawei technical support.

END