CX913 Switch Module V100R001C00 User Guide 22

This document describes the CX913 10GE switch module (CX913 for short) of the Tecal E9000 server in terms of its features, installation, removal, and configuration. This document applies to the CX913 whose GE/10GE switching planes use the software versions of 1.1.x.x.x, and 1.23-1.99.
Rate and give feedback :
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Removing the CX913

Removing the CX913

This topic describes how to remove the CX913 from the E9000 chassis.

Scenarios

Remove the CX913 from the E9000 chassis. Before the operation, become familiar with the hardware devices.

To replace a switch module, see section "Replacing a Switch Module" in the E9000 Server V100R001 User Guide.

Impact on the System

After the switch module is removed, all services running on the switch module stop.

Prerequisites

Tools

The following tools are available:

  • Protective gloves.
  • Electrostatic discharge (ESD) gloves.
  • Phillips screwdriver (PH2 is 6 mm or 0.25 in.).

Workflow

Figure 3-9 Removal process

Procedure

  1. Determine the CX913 to be removed. Figure 3-10 shows the slot numbers.

    Figure 3-10 Slot numbers

  2. Determine the connection relationships between signal cables and ports on the CX913. Figure 3-11 shows the port types and numbers of the CX913.

    Figure 3-11 Port types and numbers

    1

    BMC serial port

    2

    SYS serial port

    3

    GE electrical port(reserved)

    4

    10GE optical port

    5

    8G FC optical port

    -

    -

  3. (Optional) Remove a serial cable, as shown in Figure 3-12.

    Figure 3-12 Removing a serial cable
    NOTE:

    The BMC serial port, SYS serial port, are standard RJ-45 ports and are disconnected in the same way.

  4. Remove a 10GE or FC optical fiber and optical module.

    1. Remove the optical fiber from the optical module. See (1) and (2) in Figure 3-13.
    2. Install the dust-proof cap for the optical module. See (3) in Figure 3-13.
      Figure 3-13 Removing an optical fiber
      NOTE:

      Use the same method to remove an optical fiber from a 10GE optical port or 8G FC optical port.

    3. Determine the optical module type and removal position based on site requirements.
    4. Remove the optical module horizontally from the optical port, as shown in Figure 3-14.
      Figure 3-14 Removing an optical module

  5. Remove the CX913.

    1. Use a Phillips screwdriver to loosen the two M3 captive screws. See (1) in Figure 3-15.
      Figure 3-15 Removing the switch module
    2. Raise the two ejector levers on the CX913 completely and pull the switch module horizontally out of the chassis. See (2) and (3) in Figure 3-15.
    3. Lower the ejector levers on the CX913. See (4) in Figure 3-15.
      NOTICE:

      An ESD bag holds only one switch module.

    4. Place the removed switch module into an ESD bag.

  6. Install a switch module filler panel.

    1. Raise the two handles on the switch module filler panel and push the filler panel horizontally into the chassis as far as it will go. See (1) in Figure 3-16.
      Figure 3-16 Installing a switch module filler panel
    2. Lower the two handles on the switch module filler panel. See (2) in Figure 3-16.
    3. Use a Phillips screwdriver to tighten the two M3 captive screws on the switch module filler panel. See (3) in Figure 3-16.