E9000 Server V100R001 User Guide 24

This document describes the overview, functions, structure, installation, and configuration methods of the E9000.
Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Technical Specifications

Technical Specifications

This section describes the physical, environmental, and power supply specifications of the E9000 chassis.

Table 2-16 Physical specifications

Item

Specifications

Dimensions (H x W x D)

  • Chassis: 530.2 mm (12U) x 442 mm x 840 mm (20.87 in. x 17.40 in. x 33.07 in.)
  • PSU: 40.5 mm x 126 mm x 285 mm (1.59 in. x 4.96 in. x 11.22 in.)
  • Fan module: 84 mm x 82 mm x 296.3 mm (3.31 in. x 3.23 in. x 11.67 in.)

Cabinet dimensions

  • For a 1200 mm (47.24 in.) deep cabinet, the minimum internal width of the cabinet is greater than 473 mm (18.62 in.); the distance between the front mounting bar and the front inner side is 65 mm (2.56 in.) to 115 mm (4.53 in.); the distance between the front and rear mounting bars is 689 mm (27.13 in.) to 929 mm (36.57 in.). The recommended guide rail is 21240817, which does not occupy extra space.
  • For a 1100 mm (43.31 in.) deep cabinet, the minimum internal width of the cabinet is greater than 473 mm (18.62 in.); the distance between the front mounting bar and the front inner side is 65 mm (2.56 in.) to 115 mm (4.53 in.); the distance between the front and rear mounting bars is 689 mm (27.13 in.) to 929 mm (36.57 in.). The recommended guide rail is 21240817, which does not occupy extra space.
  • For a 1000 mm (39.37 in.) deep cabinet, the minimum internal width of the cabinet is greater than 449 mm (17.68 in.); the distance between the front mounting bar and the front inner side is 65 mm (2.56 in.) to 115 mm (4.53 in.); the distance between the front and rear mounting bars is 500 mm (19.69 in.) to 858 mm (33.78 in.). The recommended guide rail is 21241598, which occupies 1U of space.
NOTE:
  • Ensure that the distance between the front and rear posts does not exceed the 840 mm (33.07 in.) chassis depth. In addition, ensure that sufficient space is reserved inside the cabinet for routing cables between PDUs and other modules.
  • If the cabinet is customized or is to be transported with the guide rails installed, you can find guide rail information in the BOM.
  • The following figure shows the minimum internal width of the cabinet and the distance between the front and rear mounting bars.

Color

Black

Weight

Net weight:

  • Empty chassis (including midplane): 70 kg (154.35 lb)
  • Fully configured chassis: ≤ 230 kg (507.15 lb)

Packing materials:

  • Chassis packing materials: 30 kg (66.15 lb)
  • Half-width node packing materials: 2.3 kg (5.07 lb)
  • Full-width node packing materials: 3.6 kg (7.94 lb)

Floor bearing capacity

The weight of a cabinet without a chassis is about 200 kg (441.00 lb). A cabinet occupies an area of about 1.44 m2 (15.50 ft.2). The following lists the requirements for the floor bearing capacity based on the number of E9000 chassis in a cabinet:

  • One E9000 chassis: 347.2 kg/m2 (0.49 bf/in.2)
  • Two E9000 chassis: 555.5 kg/m2 (0.79 bf/in.2)
  • Three E9000 chassis: 763.9 kg/m2 (1.09 bf/in.2)
Table 2-17 Environmental specifications

Item

Specifications

Temperature

Server:

  • Operating temperature: 5°C to 40°C (41°F to 104°F) (ASHRAE Class A3 compliant)
  • Storage temperature: –40°C to +65°C (–40°F to +149°F)
  • Temperature change rate: < 20°C/h (36°F/h)

PSU:

  • Operating temperature: –5°C to +50°C (23°F to 122°F)
  • Storage temperature: –40°C to +85°C (–40°F to +185°F)

Fan module:

  • Operating temperature: –10°C to +70°C (14°F to 158°F)
  • Storage temperature: –40°C to +75°C (–40°F to +167°F)

Humidity

  • Operating humidity: 5% RH to 85% RH (non-condensing)
  • Storage humidity: 5% RH to 95% RH (non-condensing)
  • Humidity change rate: < 20% RH/h

Altitude

  • CH140 and CH140 V3 compute nodes

    At an altitude of 900 m (2952.72 ft.), the highest operating temperature is 35°C (95°F).

  • Other modules

    At an altitude of 900 m (2952.72 ft.), the highest operating temperature is 40°C (104°F).

If the device is used at an altitude between 900 m (2952.72 ft.) and 5000 m (16404.00 ft.), the highest operating temperature decreases by 1°C (1.8°F) for every increase of 300 m (984.24 ft.) in altitude. At an altitude of over 3000 m (9842.4 ft.), only Titanium PSUs can be used.

Noise

The data listed in the following represents the declared A-weighted sound power levels (LWAd) and declared average bystander position A-weighted sound pressure levels (LpAm) when the server is operating at an ambient temperature of 23°C (73.4°F). Noise emissions are measured in accordance with ISO 7999 (ECMA 74) and declared in accordance with ISO 9296 (ECMA 109).

Idle:

  • LWAd: 7.2 Bels
  • LpAm: 53 dBA
NOTE:

The actual sound levels generated during server operation vary depending on the server configuration, load, and ambient temperature.

Corrosive gas pollutant

  • Corrosion rate of the copper test piece: less than 300 Å/month (in compliance with the ANSI/ISA-71.04-2013 gas corrosion level G1)
  • Corrosion rate of the silver test piece: less than 200 Å/month

Particulate pollutant

  • The ISO14664-1 Class 8 requirements are met.

    It is recommended that a professional company monitor particulate pollutants in the equipment room.

  • There is no explosive, conductive, magnetic, or corrosive dust in the equipment room.

Heat dissipation per slot

  • Compute node slot:

    35°C (95°F)

    • Half-width slot: 900 W
    • Full-width slot: 1800 W

    40°C (104°F)

    • Half-width slot: 700 W
    • Full-width slot: 1400 W
  • Switch module slot: 280 W
  • Management module slot: 80 W
Table 2-18 PSU specifications

Item

Specifications

Input voltage

  • DC PSU: –48 V DC to –60 V DC
  • AC PSU: 100 V AC to 130 V AC, 200 V AC to 220 V AC, and 220 V AC to 240 V AC; 50 Hz or 60 Hz

Maximum input current

  • 3000 W AC PSU: 16 A
  • 2000 W AC PSU: 10 A
  • 2500 W DC PSU: 80 A
NOTE:
  • The 3000 W AC PSU uses an internal 30 A fuse.
  • The 2000 W AC PSU uses an internal 20 A fuse.
  • The 2500 W DC PSU uses an internal 100 A fuse.

Output voltage

12.3 V DC

PSU rated power

A chassis houses a maximum of six PSUs. The following lists the rated power of each type of PSU:

  • 3000 W AC PSU:
    • 1200 W (for 100 V AC to 130 V AC input)
    • 2500 W (for 200 V AC to 220 V AC input)
    • 3000 W (for 220 V AC to 240 V AC input)
  • 2000 W AC PSU:
    • 800 W (for 100 V AC to 130 V AC input)
    • 1800 W (for 200 V AC to 220 V AC input)
    • 2000 W (for 220 V AC to 240 V AC input)
  • 2500 W DC PSU: 2500 W (for –48 V DC to –60 V DC input)