TP48200A-HX09A3, TP48200A-HX09A4, TBC300A-DCA3, TBC300A-DCA5, TBC300A-TCA2 Outdoor Power System User Manual

This document describes the DC power systems in terms of their features, configurations, components, and maintenance methods.
Rate and give feedback :
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Environmental Specifications

Environmental Specifications

Table 5-1  Environmental specifications

Item

Specifications

Operating temperature

  • TP48200A-HX09A3: -40°C to +45°C with 1120 W/m2 solar radiation
  • TP48200A-HX09A4: -40°C to +45°C with 1120 W/m2 solar radiation
  • TBC300A-DCA3: -10°C to +45°C with 1120 W/m2 solar radiation
  • TBC300A-DCA5: -40°C to +45°C with 1120 W/m2 solar radiation
  • TBC300A-TCA2: -40°C to +45°C with 1120 W/m2 solar radiation

Transportation temperature

-40°C to +70°C

Storage temperature

-40°C to +70°C

Operating humidity

5%–95% RH (non-condensing)

Transportation humidity

5%–95% RH (non-condensing)

Storage humidity

5%–95% RH (non-condensing)

Altitude

0-4000 m

When the altitude ranges from 2000 m to 4000 m, the operating temperature decreases by 1°C for each additional 200 m.