Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Identifying Circuit Breaker Faults

Identifying Circuit Breaker Faults

The following indicate that the circuit breaker is faulty:
  • The circuit breaker cannot be switched to ON/OFF after the short circuit fault for its end circuit is rectified.
  • When the circuit breaker is switched to ON and its input voltage is normal, the voltage between the two ends of the circuit breaker exceeds 1 V.
  • The input voltage is normal, but the resistance between both ends of the circuit breaker is less than 1 kΩ when the circuit breaker is OFF.