TP48200A-HX09A3, TP48200A-HX09A4, TBC300A-DCA3, TBC300A-DCA5, TBC300A-TCA2 Outdoor Power System User Manual

This document describes the DC power systems in terms of their features, configurations, components, and maintenance methods.
Rate and give feedback :
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Configurations

Configurations

Table 2-1 describes the system configurations for the TP48200A-HX09A3 and TP48200A-HX09A4. Table 2-2 describes the system configurations for the TBC300A-DCA3, TBC300A-DCA5 and TBC300A-TCA2.

Table 2-1  TP48200A-HX09A3 and TP48200A-HX09A4 configurations

Item

TP48200A-HX09A3 and TP48200A-HX09A4

Application environment

Class C

Heater

None

Temperature control unit (TCU)

Equipment compartment: heat exchanger

Cabinet

Provides 10 U space for customer equipment.

PDU

  • AC PDU: AC input circuit breaker, AC output circuit breaker and terminal, and maintenance socket
  • DC PDU: battery low voltage disconnection (BLVD), load low voltage disconnection (LLVD), and battery branch

Rectifier

A maximum of four R4850G1s or R4850N1s can be configured.

Site monitoring unit (SMU)

SMU02B

User interface module (UIM)

UIM02C

Sensor

  • Mandatory: one door status sensor and one ambient temperature sensor
  • Optional: one smoke sensor, one ambient temperature and humidity sensor, and one water sensor

Lamp

Optional: one lamp

Maximum output power

12 kW

Table 2-2  TBC300A-DCA3, TBC300A-DCA5, and TBC300A-TCA2 configurations

Item

TBC300A-DCA3

TBC300A-DCA5

TBC300A-TCA2

Application environment

Class B

Class B

Class C

Heater

None

Enabled

TEC with a heating function

Temperature control unit (TCU)

Battery compartment: direct ventilation and TCUA control box

Battery compartment: direct ventilation and TCUA control box

Battery compartment: TEC and TCUA control box

Sensor

One door status sensor and one battery temperature sensor

Battery

Battery compartment of two layers: two front-access battery strings (12 V/100 Ah) can be configured.

NOTE:
  • Class B environments refer to indoor environments in which the ambient temperature and humidity are not controlled and outdoor environments (with simple shielding measures) where humidity can reach 100%.
  • Class C environments refer to sea environments or outdoor land environments (with simple shielding measures) near pollution sources. If a site is near a pollution source, it is at most 3.7 km away from salt water, such as the sea and salt lakes, 3 km away from heavy pollution sources, such as smelteries, coal mines, and thermal power plants, 2 km away from medium pollution sources, such as chemical, rubber, and galvanization industries, and 1 km away from light pollution sources, such as packing houses, tanneries, and boiler rooms.