Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
TEC04C Specifications

TEC04C Specifications

Table 5-7  TEC04C specifications

Item

Specifications

Rated voltage

-48 V DC

Rated cooling capacity (L32/L32)

200 W

Heating capacity

> 300 W

Rated Cooling Power Consumption

300 W

Operating environment

-40°C to +40°C

Relative humidity

5%-95% RH

Storage environment

-40°C to +70°C, complying with the ETS 300 019-1-1, Class 1.2.

Altitude

< 4700 m

Service life

10 years

Mean time between failures (MTBF)

> 100,000 hours

Dimensions (H x W x D)

400 mm x 180 mm x 200 mm

Weight

6.4 kg

Reverse connection prevention for DC power

Supported

Operating voltage

-36 V DC to -60 V DC

Temperature sensor

Detecting range: -20°C to +80°C (precision: ±2°C)