TP48200A-HX09A3, TP48200A-HX09A4, TBC300A-DCA3, TBC300A-DCA5, TBC300A-TCA2 Outdoor Power System User Manual

This document describes the DC power systems in terms of their features, configurations, components, and maintenance methods.
Rate and give feedback :
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
PDU

PDU

AC PDU

Figure 3-6 and Figure 3-7 show the AC PDU of the TP48200A-HX09A3. Figure 3-8 and Figure 3-9 show the AC PDU of the TP48200A-HX09A4. Table 3-1 shows the AC PDU configurations.

Figure 3-6  AC PDU of the TP48200A-HX09A3

(1) AC input circuit breakers (2) AC input terminal (neutral wire) (3) AC SPD
Figure 3-7  AC output unit (all-purpose socket and circuit breaker)

(1) Multi-purpose socket (2) Circuit breaker (3) AC output circuit breaker and neutral wire terminal
Figure 3-8  AC PDU of the TP48200A-HX09A4

(1) AC input circuit breakers (2) AC input terminal (neutral wire) (3) AC SPD
Figure 3-9  AC output unit (all-purpose socket and circuit breaker)
(1) Multi-purpose socket (2) Residual current device (RCD) (3) AC output circuit breaker and neutral wire terminal
Table 3-1  AC PDU configurations

Item

TP48200A-HX09A3

TP48200A-HX09A4

Input system

220/380 V AC three-phase, four-wire input system, compatible with 220 V AC single-phase input systems

110 V AC dual-live wire

AC input circuit breaker

One three-pole 63 A switch

One 2-pole 125 A circuit breaker

AC surge protection

Nominal surge discharge current: 20 kA (8/20 µs); maximum surge discharge current: ±40 kA (8/20 µs)

Nominal surge discharge current: 30 kA (8/20 µs); maximum surge discharge current: ±60 kA (8/20 µs)

AC output circuit breaker

One 1-pole 16 A circuit breaker

One 2-pole 16 A circuit breaker (220 V AC output)

Maintenance socket and its protection mode

Multi-purpose socket and 16 A circuit breaker

Multi-purpose socket (110 V AC output) and 10 A circuit breaker

DC PDU

Figure 3-10 shows the DC PDU of the TP48200A-HX09A3. Figure 3-11 show the DC PDU of the TP48200A-HX09A4. Table 3-2 shows the DC PDU configurations.

Figure 3-10  DC PDU of the TP48200A-HX09A3

(1) BLVD circuit breakers (2) LLVD circuit breakers (3) Battery circuit breakers
Figure 3-11  DC PDU of the TP48200A-HX09A4

(1) BLVD circuit breakers (2) LLVD circuit breakers (3) Battery circuit breakers
Table 3-2  DC PDU configurations

Item

TP48200A-HX09A3

TP48200A-HX09A4

Battery circuit breakers

Two 1-pole 125 A

Two 1-pole 125 A

BLVD circuit breakers

Two 1-pole 16 A and two 1-pole 10 A c

One 1-pole 80 A, two 1-pole 25 A, and one 1-pole 10 A

LLVD circuit breakers

One 1-pole 80 A and six 1-pole 32 A

One 1-pole 80 A and six 1-pole 25 A

Others

NOTE:
  • The battery cabinet TCUA uses one 10 A BLVD circuit breaker.
  • One load circuit breaker is used for a lamp if there is one.