TP48200A-HX09A3, TP48200A-HX09A4, TBC300A-DCA3, TBC300A-DCA5, TBC300A-TCA2 Outdoor Power System User Manual

This document describes the DC power systems in terms of their features, configurations, components, and maintenance methods.
Rate and give feedback :
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Batt. Low Temp.

Batt. Low Temp.

NOTE:
This alarm is generated only for the power system that has a battery temperature sensor installed.

Possible Causes

  • The low battery temperature alarm threshold is incorrectly set on the SMU.
  • The battery temperature control system is faulty.
  • The battery temperature sensor is faulty.

Measures

  1. Check whether the low battery temperature alarm threshold (-10°C by default) is correctly set. If not, set the threshold to the correct value.
  2. Check whether the temperature control system for the battery compartment is faulty. If so, rectify the fault. The alarm is cleared when the temperature in the battery compartment becomes normal.
  3. Check whether the battery temperature sensor is faulty. If so, replace the battery temperature sensor.