Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Checking the Cabinet/Rack

Checking the Cabinet/Rack

Table 4-2 describes the requirements for the cabinet/rack where the CE8800&7800&6800&5800 series switches can be installed.

Table 4-2 Requirements for the cabinet/rack
Item Requirement
Width Use a standard 19-inch four-post cabinet or rack. CE8850-32CQ-EI and the CE7800&6800&5800 series switches are 43.6 mm high, and CE8850-64CQ-EI, CE8860, CE8861, and CE8868 are 88.1 mm high. With their widths in compliance with industry standards, these switches can be installed in a standard 19 inch cabinet/rack.
Depth A separately purchased non-standard cabinet/rack must have sufficient space for chassis installation. The cabinet for a CE5800, CE6800 (420 mm deep), or CE8850-32CQ-EI switch must be no less than 600 mm deep, and the cabinet for a CE6800 (600 mm deep), CE7800, CE8850-64CQ-EI, CE8860, CE8861, or CE8868 switch must be no less than 800 mm deep.
Heat dissipation The CE8800&7800&6800&5800 series switches use front-to-back or back-to-front airflow design. The cabinet must meet the requirement of the airflow.
Grounding The cabinet must have reliable ground points to ground the chassis.
Distance between front and rear mounting rails When the CE8800&7800&6800&5800 series switches need to be installed in the same cabinet with a CE12800 switch, keep the distance between the front and rear mounting rails in the range of 700 mm to 800 mm.
Cabling space On a switch, the side with power modules and fan modules is the power supply side, and the side with service ports is the port side. To ensure sufficient cabling space, reserve at least 130 mm of distance from the port side to the interior side of the cabinet door, and at least 70 mm from the power supply side to the interior side of the cabinet door.

Figure 4-1 shows the points from which to take measurements for the cabinet width (a), the cabinet depth (b), and the distance between front and rear mounting rails (c).

Figure 4-1 Measuring a cabinet