RH5885 V3 Server V100R003 User Guide 32

This document describes the appearance, specifications, parameters, and structure of the RH5885 V3, and how to install an OS, replace parts, and install, remove, configure, and troubleshoot the server.
Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Installation Overview

Installation Overview

Checking the Installation Environment

To ensure proper installation and operating of the RH5885 V3, prepare the installation environment before installation. Check that the rack, space, temperature, and humidity all conform to the following requirements.

Space Requirements

  • Install the RH5885 V3 in an access restricted area.
  • Keep the areas where equipment is located clean and tidy.
  • Allow for an 800 mm (31.50 in.) clearance between walls, and the front or rear doors of the cabinet to facilitate heat dissipation and device maintenance.

Rack Requirements

  • Use a general rack that is 19 inches wide and more than 1000 mm (39.37 in.) deep and complies with the International Electrotechnical Commission 297 (IEC 297) standard.
  • Install air filters on the rack doors.
  • Provide AC power supply from the rear of the rack.

Temperature and Humidity Requirements

  • Use temperature control devices all year long in any climates.
  • Use humidifiers or mops regularly to increase ambient humidity in dry areas.
  • Use dehumidifiers to reduce ambient humidity in wet areas.
Table 3-1 Temperature and humidity requirements in the equipment room

Item

Description

Temperature

10°C to 40°C (50°F to 104°F)

Humidity

8% RH to 90% RH (non-condensing)

Installation Rules

  • The RH5885 V3 is 4 U high and can be installed in a standard 19-inch cabinet. Servers can be stacked in a cabinet. If the cabinet space is sufficient, the distance between two adjacent servers is 1 U high.
  • The RH5885 V3 is heavy. Install it in the lower part of a rack to keep balance of the rack.