FusionServer Pro Rack Server iBMC Alarm Handling 30

This document describes iBMC alarms in terms of the meaning, impact on the system, possible causes, and handling suggestions.
Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
ALM-0x12000019 Right Mounting Ear Not Detected (Chassis, Minor Alarm)

ALM-0x12000019 Right Mounting Ear Not Detected (Chassis, Minor Alarm)

Description

Alarm message:

Right mounting ear is not present.

This alarm is generated when the right mounting ear of the server cannot be detected.

Alarm object: chassis

Attribute

Alarm ID Alarm Severity Auto Clear

0x12000019

Minor

Yes

Parameters

Name Meaning

-

-

Impact on the System

  • The inlet temperature cannot be obtained.
  • The power button on the mounting ear is unavailable.
  • The UID button on the mounting ear is unavailable.

Possible Causes

  • The cable of the right mounting ear is not securely connected.
  • The cable of the right mounting ear is faulty.
  • The right mounting ear is faulty.

Procedure

  1. Remove and reconnect the cable to the right mounting ear. Then, check whether the alarm is cleared.

    For details about how to connect the cable, see the user guide of the server you use.

    • If yes, no further action is required.

    • If no, go to 2.

  2. Replace the cable of the right mounting ear. Then, check whether the alarm is cleared.

    • If yes, no further action is required.

    • If no, go to 3.

  3. Replace the mounting ear.Then, check whether the alarm is cleared.

    For details about how to replace the mounting ear, see the user guide of the server you use.

    • If yes, no further action is required.

    • If no, go to 4.

  4. Contact Huawei technical support.