MA5600T, MA5603T, and MA5608T Hardware Description 25

This manual describes the Huawei MA5600T, MA5603T, and MA5608T hardware specifications, such as dimensions, weight, power consumption, capacity, structure, chassis, slots, boards, power modules, and optical modules.
Rate and give feedback :
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
ETP4890 Power System

ETP4890 Power System

An AC-powered cabinet uses the ETP4890 power system to convert the AC power to the DC power for power distribution. The small and modular ETP4890 power system supports easy installation and maintenance and effective LCD interface management. The power system supports a maximum of 90 A output current.

Function

The ETP4890 power system supports the following functions:
  • Converts AC power to DC power and provides the DC power for communication devices.
  • Communicates with the upper device using a COM or an RS485/RS232 serial port; sends control signals based on the values of monitored parameters or the control command sent by the upper device; detects power distribution parameters, power supply module parameters, and auxiliary digital parameters in real time.
  • Connects to one to two groups of lead acid batteries and uses a monitoring module to manage the batteries; provides complete management for battery charging and discharging, ensuring efficient battery usage.
  • Connects to a sensor transfer box using a DB50 port, detecting analog parameters and digital parameters, and outputting control signals.
  • Uses a monitoring module to monitor all running parameters for the ETP4890 power system in real time; determines the working status; reports alarms in a timely manner.
  • Clearly displays the monitoring and alarm information on the liquid crystal display (LCD) of the monitoring module; allows operations such as parameter setting on the LCD of the monitoring module.

Appearance

Figure 6-20 shows the appearance of the ETP4890 power system.

Figure 6-20  ETP4890 power system

Configuration

Table 6-14 lists the components of the ETP4890 power system.

Table 6-14  Component configuration of the ETP4890 power system

Component

Quantity

AC and DC power distribution subrack

1

Monitoring module

1

Power supply module R4830N1/R4830G1

1 to 3 (optional; by default, the R4830N1 is configured)

The ETP4890 power system can be configured with three power supply modules, which are connected in parallel for output.

Table 6-15 shows the mapping between the quantity of power supply modules in the ETP4890 power system and the maximum output current.

Table 6-15  Mapping between the quantity of power supply modules of the ETP4890 power system and the maximum output current

Quantity of Power Supply Modules

Maximum Output Current

1

  • 30 A (at 55°C)
  • 25 A (at 60°C)

2

  • 60 A (at 55°C)
  • 50 A (at 60°C)

3

  • 90 A (at 55°C)
  • 75 A (at 60°C)

Communication Ports on the Monitoring Module

Table 6-16 lists the communication ports on the monitoring module. A user can set the baud rate of the device using the LCD interface of the monitoring module.

Table 6-16  Communication ports on the monitoring module

Communication Port

Communication Mode

Communication Parameter

Description

COM

RS485/RS232

Baud rate: 9600 bit/s or 19200 bit/s

Used as a serial port, communicating with the upper device

RS485/RS232

RS485/RS232

Baud rate: 9600 bit/s or 19200 bit/s

Used as a serial port, supporting the northbound/southbound communications

NOTE:
By default, the ETP4890 power system is equipped with a monitoring module, which is capable of the inband management (SMU01B). The COM port cannot be used as a network port.

Indicators

Table 6-17 lists the indicators on the power supply module of the ETP4890 power system.

Table 6-17  Indicators on the power supply module of the ETP4890 power system

Indicator

Color

Status

Description

Power indicator

Green

Steady on

Normal

Blinking at a frequency of 0.5 Hz

There is AC input, and the power supply module is in the manual query state.

Blinking at a frequency of 4 Hz

Data is being loaded online.

Off

There is no AC input.

Alarm indicator

Yellow

Steady on

A protection mechanism is triggered. After the fault is rectified, the power supply module can be restored to the normal state.

Blinking

Communication between the power supply module and the site monitoring module is interrupted.

Off

Normal

Fault indicator

Red

Steady on

An unrecoverable fault occurs.

Blinking

The power supply module equipped with the EMU does not match the actual power supply module.

Off

Normal

Table 6-18 lists the indicators on the monitoring module.

Table 6-18  Indicators on the monitoring module

Indicator

Color

Status

Description

RUN

Green

Off

The monitoring module is faulty or there is no DC power input.

Blinking at a frequency of 0.5 Hz

The monitoring module is working properly and communicating with the upper device properly.

Blinking at a frequency of 4 Hz

The monitoring module works properly but does not communicate with the upper device properly.

ALM

Red

Off

The system does not generate any critical alarms.

Steady on

The system generates critical alarms.

Input Terminal

The ETP4890 power system supports 220 V AC input.Figure 6-21 shows the input terminals in the ETP4890 power system.

Figure 6-21  Input terminals in the ETP4890 power system

Output Terminal

The ETP4890 power system supports eight groups of output terminals. The left-side eight output terminals are negative and the right-side eight output terminals are positive.

Figure 6-22 shows the output terminals in the ETP4890 power system.

Figure 6-22  Output terminals in the ETP4890 power system

Table 6-19 lists the Specifications of the output terminals.

Table 6-19  Specifications of the output terminals

Port

Circuit Breaker

LOAD1

10 A

LOAD2

30 A

LOAD3

40 A

LOAD4

40 A

BATT

80 A

Figure 6-23 shows the output branch circuit breaker in the ETP4890 system.

Figure 6-23  Output branch circuit breaker in the ETP4890 system

Specifications

Table 6-20 lists the specifications of the ETP4890 power system.

Table 6-20  Specifications of the ETP4890 power system

Specification Class

Specification

Description

Environment conditions

Operating temperature

-40°C to +70°C
NOTE:

The power system can work at a temperature of 70°C for 8 hours.

Operating humidity

5% to 95% (no condensation)

Altitude

0 m to 4000 m

(Note that in the range of 2000 m to 4000 m, the operating temperature decreases by 1°C when the altitude increases by 200 m.)

AC input

Mode

mono-phase, dual-live wire

Voltage

85 V AC to 290 V AC (rated value: 110 V/220 V)

Frequency

45 Hz to 66 Hz (rated value: 50 Hz)

Power factor

≥ 0.99 in the case of a rated load

Power supply module peak efficiency

  • R4830N1: 94%
  • R4830G1: 96%

DC output

Voltage

-42 V to -58 V

Default voltage

-53.5 V

Maximum power

  • R4830N1: 4815 W (input voltage: 176 V AC to 290 V AC; if the temperature is higher than 55°C, power decreases linearly); 2407.5 W (input voltage: 85 V AC to 175 V AC; if the temperature is higher than 55°C, power decreases linearly)
  • R4830G1: 4800 W (input voltage: 176 V AC to 290 V AC; if the temperature is higher than 55°C, power decreases linearly); 2400 W (input voltage: 85 V AC to 175 V AC; if the temperature is higher than 55°C, power decreases linearly)
NOTE:
Maximum output power of the system = Number of the configured power supply modules x Output power of each power supply module

Regulated voltage precision

≤ ±0.6%

Peak noise voltage

≤ 200 mV (0 MHz to 20 MHz)

Structure

Dimensions (H x W x D) without brackets

86.1 mm x 442 mm x 255 mm

Weight

≤ 10 kg (including three 30 A power supply modules and one SMU01B monitoring module)

Protection class

IP20

Installation mode

Installed in an IEC cabinet or an ETSI cabinet with brackets

Maintenance mode

Front access

Cooling method

Air cooling, with the built-in fan in the power supply module