MA5600T, MA5603T, and MA5608T Hardware Description 25

This manual describes the Huawei MA5600T, MA5603T, and MA5608T hardware specifications, such as dimensions, weight, power consumption, capacity, structure, chassis, slots, boards, power modules, and optical modules.
Rate and give feedback :
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
C3-Type DC PDU

C3-Type DC PDU

This topic provides the appearance and main performance specifications of the C3-type DC PDU, and describes the power distribution principle of the PDU.

Appearance

Figure 6-8 and Figure 6-9 show the appearance of the C3-type DC PDU.

Figure 6-8  Appearance of the C3-type DC PDU (with cover)

Figure 6-9  Appearance of the C3-type DC PDU (without cover)

Function

The C3-Type DC PDU provides the following functions:

  • Short-circuit protection and overload protection
  • The functions such as over-voltage protection, lightning proof, and filter are not provided.

Power Distribution Principle

Figure 6-10 shows the power distribution principle of the C3-Type DC PDU.

Figure 6-10  Diagram of the power distribution principle of the C3-Type DC PDU

Input Terminal

Figure 6-11 shows the input terminals of the C3-type DC PDU.

Figure 6-11  Input terminals of the C3-type DC PDU

The C3-type DC PDU supports two -48 V DC/-60 V DC inputs. The connections of the input terminals are as follows:

  • RTN1 (+) connects to RTN of the first channel DC power supply.
  • NEG1 (-) connects to NEG of the first channel DC power supply.
  • PGND connects to the ground cable.
  • RTN2 (+) connects to RTN of the second channel DC power supply.
  • NEG2 (-) connects to NEG of the second channel DC power supply.
NOTE:

By default, the two channels of input power are provided by different power sources. To use the same power source to provide two channels of input power, connect a jumper to the terminal of each channel, as shown in Figure 6-10.

Output Terminal

Figure 6-12 shows the output terminals of the C3-type DC PDU.

Figure 6-12  Output terminals of the C3-type DC PDU

-48 V//-60 V Output Control Switch

Figure 6-13 shows the -48 V/-60 V output control switch of the C3-type DC PDU.

Figure 6-13  -48 V/-60 V output control switch of the C3-type DC PDU

Table 6-10 lists the mapping between the output terminals, control switches and service subracks.

Table 6-10  Mapping between the output terminals, control switches and service subracks

Terminal Silkscreen

Control Switch

Load

48V1, 48V1

SW1

The first service subrack (from bottom to top)

BGND, BGND

48V2, 48V2

SW2

The second service subrack (from bottom to top)

BGND, BGND

48V3, 48V3

SW3

The first service subrack (from bottom to top)

BGND, BGND

48V4, 48V4

SW4

The second service subrack (from bottom to top)

BGND, BGND

Specification

Table 6-11 shows the main performance specifications of the C3-Type DC PDU.

Table 6-11  Main performance specifications of the C3-Type DC PDU
Item Performance Specification

Input feature

Rated input voltage

-48 V to -60 V DC

Input voltage

-38.4 V to -72 V DC

Mode of input power

Two channels of DC input power. By default, the two channels of input power are provided by different power sources. To use the same power source to provide two channels of input power, connect a jumper to the terminal of each channel, as shown in Figure 6-10.

Maximum input current

Maximum input current of each channel is 80 A.

Input terminal

M8 OT terminal

Output feature

Rated output voltage

-48 V to -60 V DC

output voltage

-38.4 V to -72 V DC

Output channel

Eight channels of output power, controlled by four air breakers (Each air breaker controls two channels of output power.)

Fixed current of the air breaker

40 A

Output protection feature

Over-current protection. You need to restore the circuit manually.

Output terminal

Bare crimping terminal (12-10AWG).

Environment

Working temperature

-25 °C to 55 °C

Storage temperature

-40 °C to 70 °C

Relative humidity

<= 95%

Standard atmospheric pressure

70-106 KPa

Dimensions

2 U x 436 mm x 116.4 mm (Height x Width x Depth)