Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
EPS75-4815AF Power System

EPS75-4815AF Power System

The AC-powered cabinet uses the EPS75-4815AF power system to convert the AC input into the DC and then distribute the power.

Functions

The EPS75-4815AF power system converts one AC input into six DC outputs to implement the DC power distribution. It can be connected to one to two sets of batteries and use its monitoring module to manage batteries.

The EPS75-4815AF power system can also use the external sensor transfer box to collect and report the status of sensors and standby detected parameters.

NOTE:

The rectifier modules of the EPS75-4815AF power system work in the load balancing and mutual hot backup mode.

Appearance

Figure 6-24 shows the appearance of the EPS75-4815AF power system.

Figure 6-24  Appearance of the EPS75-4815AF power system

Configuration

Table 6-21 lists the component configuration of the EPS75-4815AF power system.

Table 6-21  Component configuration of the EPS75-4815AF power system

Component Name

Configuration

GERM4815T rectifier module

2 to 5 (optional)

EPMU02 monitoring module

1

Rack-EPS75-4815AF AC/DC power supply unit

1

The EPS75-4815AF power system can be configured with five rectifier modules, which are connected in parallel for output.

Table 6-22 shows the mapping between the number of rectifier modules in the EPS75-4815AF power system and the maximum output current.

Table 6-22  Mapping between the number of rectifier modules in the EPS75-4815AF power system and the maximum output current

Number of Rectifier Modules

Maximum Output Current

1

15 A

2

30 A

3

45 A

4

60 A

5

75 A

LED Description

Table 6-23 describes the LEDs on the rectifier module of the EPS75-4815AF power system.

Table 6-23  LEDs on the rectifier module of the EPS75-4815AF power system

LED

Status

Description

RUN

The green LED is on.

The rectifier module works in the normal state.

The green LED is off.

This LED is off when the red LED is on or the yellow LED is on which is not caused by the output overcurrent.

ALM

The yellow LED is on.

An alarm has been generated for the rectifier module. The possible causes are as follows:
  • The AC power is cut off or no AC power is supplied.
  • Over-temperature protection is enabled.
  • Primary protection is enabled. Specifically, the rectifier module automatic protection function is enabled due to a high voltage on the AC input end.
  • Overcurrent protection is enabled. Specifically, the rectifier module automatic protection function is enabled because the DC output current of the rectifier module exceeds the current range supported by the rectifier module.

The yellow LED blinks.

The communication of the rectifier module is interrupted.

The yellow LED is off.

The rectifier module works in the normal state.

FAULT

The red LED is on.

The rectifier module is faulty. The possible causes are as follows:
  • The AC power supply is faulty.
  • The output voltage is 0 V.
  • The fan is faulty.
  • The rectifier module output is short-circuited or does not work.

The red LED is off.

The rectifier module works in the normal state.

Table 6-24 describes the LEDs on the monitoring module of the EPS75-4815AF power system.

Table 6-24  LEDs on the monitoring module of the EPS75-4815AF power system

LED

Status

Description

RUN

The green LED is on for 1s and off for 1s repeatedly.

The monitoring module works in the normal state.

The green LED is blinking quickly.

The monitoring unit hardware is normal but the communication between the monitoring unit and the upper layer device is faulty.

The green LED is off.

The monitoring module is faulty or there is no AC power input.

ALM

The red LED is on.

The system generates a critical alarm or the battery is disconnected.

The red LED is off.

The system does not generate any critical alarm and the battery is already connected.

Input Terminals

Figure 6-25 shows the input terminals of the EPS75-4815AF power system.

Figure 6-25  Input terminals of the EPS75-4815AF power system

The EPS75-4815AF power system supports one 220 VAC input. The connections of the power system are as follows:

  • The AC-L terminal is connected to line L of the AC power cable.
  • The AC-N terminal is connected to line N of the AC power cable.
  • The grounding point is connected to the PGND cable.

Output Terminals

Figure 6-26 shows the output terminals of the EPS75-4815AF power system.

Figure 6-26  Output terminals of the EPS75-4815AF power system

Figure 6-27 shows the output tributary switches of the EPS75-4815AF power system.

Figure 6-27  Output tributary switches of the EPS75-4815AF power system

Table 6-25 shows the mapping between the output tributary switches and the loading tributaries.

Table 6-25  Mapping between the output tributary switches and the loading tributaries

Output Tributary Switch

Load Tributary

BATT.

BATT. (-) (two channels) and BATT.(+) (two channels)

LOAD1

LOAD1 (-) (two channels) and LOAD1(+) (two channels)

LOAD2

LOAD2 (-) (two channels) and LOAD2(+) (two channels)

LOAD3

LOAD3 (-), LOAD3(+)

LOAD4

LOAD4 (-), LOAD4(+)

DIP Switch

The EPS75-4815AF power system provides a DIP switch, the DIP switch is on the right middle of the monitoring module control board, which can be seen after you remove the monitoring module. The DIP switch has eight available electrical switches. ON indicates 1, and OFF indicates 0. Table 6-26 describes the settings of DIP switch.

Table 6-26  Settings of the DIP switch

Electrical Switch

Setting

Indication

Factory Default

1-5

Supported

Used to set the address of the environment monitoring module.

1: OFF

2: OFF

3: OFF

4: OFF

5: OFF

6-7

Supported

Used to set the rate of the serial port

6: ON

7: OFF

8

Not supported

-

OFF

The DIP switches 1-5 are used to set the address of the environment monitoring module, Table 6-27 shows the settings of the DIP switches.

Table 6-27  Settings of the DIP switches 1-5

5

4

3

2

1

Address Value

0

0

0

0

0

0

0

0

0

0

1

1

0

0

0

1

0

2

0

0

0

1

1

3

0

0

1

0

0

4

0

0

1

0

1

5

0

0

1

1

0

6

0

0

1

1

1

7

0

1

0

0

0

8

0

1

0

0

1

9

0

1

0

1

0

A

0

1

0

1

1

B

0

1

1

0

0

C

0

1

1

0

1

D

0

1

1

1

0

E

0

1

1

1

1

F

1

0

0

0

0

10

...

..

..

..

..

..

The DIP switches 6-7 are used to set the rate of the serial port, Table 6-28 shows the settings of the DIP switches.

Table 6-28  Settings of the DIP switches 6-7

7

6

Rate Value

0

0

4800 bit/s

0

1

9600 bit/s

1

0

19200 bit/s

Specifications

Table 6-29 lists the specifications of the EPS75-4815AF power system.

Table 6-29  Specifications of the EPS75-4815AF power system

Item

Specification

Input

  • Rated input voltage: 220 VAC (90 VAC to 290 VAC) (Note that in the range of 90 VAC to 175 VAC, the output current also decreases linearly, limited within a specified range.)
  • Maximum input current: 28 A
  • Frequency: 50 Hz (45 Hz to 65 Hz)

Output

  • Rated output voltage: -53.5 V DC
  • Voltage range: -42 V DC to -58 V DC
  • Output current:
    • LOAD1: 10 A (circuit breaker)
    • LOAD2: 30 A (circuit breaker)
    • LOAD3: 40 A (circuit breaker)
    • LOAD4: 40 A (circuit breaker)
    • BATT.: 80 A (circuit breaker)

Efficiency

≥ 90% (in rated working state)

Working temperature range

-33 °C to +65 °C.

NOTE:

In the range of +50 °C to +65 °C, the output current decreases linearly, limited within a specified range.

Cooling method

Forced air cooling, with the built-in fan in the rectifier module

Dimensions (W x D x H, excluding the mounting ears)

436 mm x 255 mm x 133 mm

Download
Updated: 2019-03-18

Document ID: EDOC1000060621