Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
How Do I Calculate the Number of Power Modules Required in CloudEngine 12800 and 12800E Series Switches?

How Do I Calculate the Number of Power Modules Required in CloudEngine 12800 and 12800E Series Switches?

The Hardware Configuration Tool helps you quickly calculate the number of power modules required in CloudEngine 12800 and 12800E series switches. The calculator is also integrated in the UniSTAR system.

You can also use the following formula to calculate the number of power modules required:

Minimum number of power modules required = Sum of maximum power consumption of all working modules in the switch/Maximum power of a single power module (integral part of the result) + 1

For example, a CE12808 switch uses 2700 W AC power modules and is configured with two CE-CMUAs, five CE-SFU08As, two CE-MPUAs, and two CE-L48XS-EC line cards. Based on the power consumption values of the cards provided in the "Cards" section of the Hardware Description and the power consumption of the chassis (including fans) and power modules, the sum of maximum power consumption of all modules can be obtained: 2519 W. Therefore, a minimum of one 2700 W power module is required.

To ensure power reliability of a CloudEngine 12800 switch, it is recommended that you use the N+N backup mode with double power supply systems so that the failure of a single power supply system will not cause power failure or restart of the switch. In the preceding example, the 1+1 backup mode is recommended.