Troubleshooting Guide

CloudEngine 16800, 12800, 12800E, 8800, 7800, 6800, and 5800 Series Switches

Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Checking the Operating Environment

Checking the Operating Environment

Devices can run properly only after the following conditions are met.

Table 4-1 lists the operating environment check items of CE12800 and CE12800E series switches. Table 4-2 lists the operating environment check items of CE8800, CE7800, CE6800, and CE5800 series switches.

Table 4-1 Operating environment check items of CE12800 and CE12800E series switches

No.

Check Item

Criteria

Result

1

Ambient temperature in the equipment room

  • Operating temperature: 0°C to 40°C (0 m to 1800 m)
    NOTE:

    When the altitude is between 1800 m and 5000 m, the operating temperature reduces 1°C every time the altitude increases 220 m.

  • Storage temperature: -40°C to +70°C

□ Satisfied

□ Unsatisfied

□ Not involved

2

Ambient humidity

Operating relative humidity: 5% RH to 85% RH (noncondensing)

If the relative humidity in the equipment room is high, you may need to install a dehumidifier. If the relative humidity in the equipment room is low, you may need to install a humidifier.

□ Satisfied

□ Unsatisfied

□ Not involved

3

Cleaning

  • The device should be clean without visible dust.
  • If the air filter door is covered by dust, clean or replace the dustproof cotton in the air filter door in time; otherwise, the heat dissipation in the chassis is affected.

□ Satisfied

□ Unsatisfied

□ Not involved

4

Heat dissipation

  • When a device is working, all fans should operate properly (except for the fans that are being cleaned).
  • The air intake vent is not covered with dust, and heat dissipation in the chassis is normal. If the air filter door is covered with dust, clean it in time. It is recommended to clean the air filter door quarterly.

□ Satisfied

□ Unsatisfied

□ Not involved

5

Cabling

  • Power cables should be separated from service cables. Power cables and service cables should be routed smoothly and neatly.

□ Satisfied

□ Unsatisfied

□ Not involved

6

Cable label

  • Cable labels are clean, correct, and standardized.

□ Satisfied

□ Unsatisfied

□ Not involved

7

Power supply system

The power supply system should run stably.
  • Rated voltage: 110 V/220 V AC
  • Rated voltage range: 100 V AC to 120 V AC or 200 V AC to 240 V AC
  • Maximum voltage range: 90 V AC to 290 V AC

□ Satisfied

□ Unsatisfied

□ Not involved

Table 4-2 Operating environment check items of CE8800, CE7800, CE6800, and CE5800 series switches

No.

Check Item

Criteria

Result

1

Position of the device

The device should be placed steadily in a flat position in a ventilated and dry environment.

□ Satisfied

□ Unsatisfied

□ Not involved

2

Ambient temperature in the equipment room

  • Operating temperature: 0°C to 40°C (0 m to 1800 m)
    NOTE:

    When the altitude is between 1800 m and 5000 m, the operating temperature reduces 1°C every time the altitude increases 220 m.

  • Storage temperature: -40°C to +70°C

□ Satisfied

□ Unsatisfied

□ Not involved

3

Ambient humidity

Operating relative humidity: 5% RH to 95% RH (noncondensing)

□ Satisfied

□ Unsatisfied

□ Not involved

4

Air conditioner in the equipment room

The air conditioner keeps running steadily so that the temperature in the equipment room is within an acceptable range.

□ Satisfied

□ Unsatisfied

□ Not involved

5

Grounding and grounding resistance

Working grounding, protection grounding, and surge protection grounding should be arranged separately in the equipment room. Joint grounding can be used if the equipment room is under limited conditions. Grounding is significant especially for outdoor devices because the outdoor devices are possibly struck by thunder.

□ Satisfied

□ Unsatisfied

□ Not involved

6

Connection to power supply

Power cables should be correctly and securely connected to the specified position of the device. The power supply indicator on the device should be steady green.

□ Satisfied

□ Unsatisfied

□ Not involved

7

Power supply system

The power supply system should run stably.
  • Rated voltage: 100 V AC to 240 V AC, 50/60 Hz
  • Maximum voltage range: 90 V AC to 290 V AC, 45 Hz to 65 Hz

□ Satisfied

□ Unsatisfied

□ Not involved

8

Ventilation channel

No sundries exist around the device. There is at least 1 U clearance between two devices to ensure efficient heat dissipation.

□ Satisfied

□ Unsatisfied

□ Not involved

9

Heat dissipation

Power modules and fan modules in a chassis have the same airflow direction. The device has the same airflow direction as that of other devices in the same cabinet.

□ Satisfied

□ Unsatisfied

□ Not involved

10

Fan module

The fan module indicator on the device should slowly blink green.

□ Satisfied

□ Unsatisfied

□ Not involved

11

Device operation

The SYS indicator on the device should slowly blink green.

□ Satisfied

□ Unsatisfied

□ Not involved