Post-Installation Checks
Table 10-1 lists the post-installation items to be checked.
No. |
Check Item |
Method |
---|---|---|
1 |
The installation position of the cabinet meets the requirement in the associated engineering design document. |
Observe |
2 |
Components are correctly installed in the cabinet. No components are loose or damaged. |
Observe |
3 |
All the screws are correctly secured. The chassis bottom is completely attached to the guide rails or tray. |
Observe |
4 |
The vertical deviation of the cabinet is less than 3 mm. You can use a plumb line to measure the vertical deviation. |
Measure |
5 |
The cabinets on the sides of the main path are aligned, with a deviation of less than 5 mm. |
Measure |
6 |
The surfaces of the cabinets in the same row are on the same plane. The cabinets are deployed close to each other. |
Observe |
7 |
The front door of a cabinet can be opened and closed easily. |
Observe |
8 |
The cable outlets on the top and bottom of the cabinet are sealed. |
Observe |
9 |
All the signal cables have passed a continuity check. |
Observe and measure |
10 |
Routes of signal cables comply with the engineering design document. |
Observe |
11 |
The signal cables are not placed on the air vent of the cabinet. |
Observe |
12 |
Signal cables are not damaged or broken and have no splices. |
Observe |
13 |
Signal cable connectors are clean and intact, and correctly connected. Wires of each signal cable are securely crimped in the connectors. |
Observe |
14 |
Signal cables do not cross each other and have sufficient slack at the bent part. (Signal cables can be crossed within 1 m outside the cabinet.) |
Observe |
15 |
Each signal cable has correct, clear, and tidy labels attached on both ends. |
Observe |
16 |
Pigtail fibers outside a cabinet are laid in a protection pipe or trough and are not squeezed by other cables or objects. |
Observe |
17 |
Optical fibers are led into a cabinet through a corrugated pipe. The corrugated pipe in the cabinet should be not more than 100 mm long and be bundled onto the cabinet. |
Observe and measure |
18 |
The bend radius of optical fibers is 20 times larger than their diameter. Generally, the bend radius should be no less than 40 mm. The path of optical fibers is not blocked by any components. |
Observe and measure |
19 |
Each pair of fibers is bundled by binding tape with appropriate force. |
Observe |
20 |
The routes of power cables and ground cables conform to the engineering design document, facilitating future maintenance and system expansion. |
Observe |
21 |
All power cables and ground cables are complete copper wires without splices. Coatings of power cables and ground cables are intact. |
Observe |
22 |
Power cables and ground cables are connected properly. The spring washer of each ground terminal is placed on the flat washer. |
Observe |
23 |
Diameters of power cables and ground cables conform to the associated engineering design document, meeting the power distribution requirements. |
Observe |
24 |
Power cables and ground cables are separated from signal cables. |
Observe |
25 |
Power cables and ground cables are routed straightly and properly bundled, with sufficient slack at the bend part. |
Observe |
26 |
The redundant part of the power cables and ground cables is cut off. |
Observe |
27 |
Power cables, ground cables, and power switches on power distribution boxes and power distribution frames are identified by correct, legible labels. |
Observe |
28 |
The lugs of the power cables and ground cables are soldered or crimped tightly. |
Observe |
29 |
Metal components in a cabinet have good electrical connections with the rack. Screw mounting holes, guide rails, and mounting brackets are not covered with insulation painting. |
Observe |
30 |
Ground busbars of adjacent cabinets are connected through busbar cables. |
Observe |
31 |
The yellow-green ground cables are correctly connected. One end of a ground cable is connected to the PGND ground bar in the power distribution cabinet, and the other end is connected to the ground point on the cabinet. Screws at both ends of the ground cable are securely fastened. |
Observe |
32 |
The removable handles are hanging at the rear of the chassis. |
Observe |
33 |
The new switch will not cause loops on the current network. For example, this switch cannot be connected to another device using two links. |
Check against the networking diagram |