Grounding Specifications for an Equipment Room
Grounding Specifications for an Equipment Room
The grounding resistance of a comprehensive communication building
should be less than or equal to one ohm. The grounding resistance
of an ordinary communication office should be less than five ohms.
The grounding resistance in an area where the earth resistance rate
is high should be less than 10 ohms.