Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Batt. High Temp.

Batt. High Temp.

NOTE:
This alarm is generated only for the power system that has a battery temperature sensor installed.

Possible Causes

  • The high battery temperature alarm threshold is incorrectly set.
  • The battery temperature control system is faulty.
  • The battery temperature sensor is faulty.

Measures

  1. Check whether the high battery temperature alarm threshold (50°C by default) is correctly set. If not, set the threshold to the correct value.
  2. Check whether the battery temperature control system is faulty. If so, rectify the fault. The alarm is cleared when the battery temperature falls within the allowed range.
  3. Check whether the battery temperature sensor is faulty. If so, replace the temperature sensor.