Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Batt Loop Trip

Batt Loop Trip

Possible Causes

  • The battery circuit breaker or fuse detection cable is loosely connected.
  • The battery circuit breaker has tripped or the battery fuse has blown.
  • The contactor is faulty.

Measures

  1. Check whether the battery circuit breaker or fuse detection cable is loosely connected. If so, reconnect the cable.
  2. Check whether the battery circuit breaker has tripped or the battery fuse has blown. If so, rectify the battery loop fault and then switch on the circuit breaker or replace the fuse.
  3. Manually switch on or switch off the battery contactor and check whether the battery current changes accordingly. If not, replace the contactor.