TP48200A-HT19C4-1, TBC300A-TCA2 Outdoor Power System User Manual

Rate and give feedback :
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Configurations

Configurations

Table 2-1 describes the system configurations for the TP48200A-HT19C4-1 and TBC300A-TCA2.

Table 2-1  Configurations

Item

TP48200A-HT19C4-1

TBC300A-TCA2

Application environment

Class C

Temperature control unit (TCU)

  • Equipment compartment: HXC150S heat exchanger
  • Battery compartment: TEC

Battery compartment: TEC

Space for customer equipment

16 U

N/A

AC input system

110 V AC dual-live wire

N/A

AC input circuit breaker

One 2-pole 100 A circuit breaker

N/A

(Optional) AC output circuit breaker

One 2-pole 10 A circuit breaker and one 3-pole maintenance socket protected by an 10 A electric residual current device (RCD).

N/A

DC output

  • Battery low voltage disconnection (BLVD): two 1-pole 10 A circuit breakers and four 1-pole 16 A circuit breakers
  • Load low voltage disconnection (LLVD): one 1-pole 100 A circuit breaker, one 1-pole 63 A circuit breaker, and four 1-pole 32 A circuit breakers
  • Battery route: two 1-pole 125 A circuit breakers

N/A

Rectifier

A maximum of four R4850G2s or R4830G2s can be configured.

N/A

Site monitoring unit (SMU)

One SMU02B

N/A

User interface module (UIM)

One UIM02C

N/A

Sensor

  • Mandatory: one battery temperature sensor, one ambient temperature sensor in the equipment compartment, and one door status sensor
  • Optional: one smoke sensor, one ambient temperature and humidity sensor, and one water sensor.

One door status sensor and one battery temperature sensor.

Battery

The battery compartment with two layers supports a maximum of two 12 V, 150 Ah battery strings.

Battery compartment of two layers: two front-access battery strings (12 V/100 Ah) can be configured.

Maximum output power

12 kW

NOTE:
Class C environments refer to sea environments or outdoor land environments (with simple shielding measures) near pollution sources. If a site is near a pollution source, it is at most 3.7 km away from salt water, such as the sea and salt lakes, 3 km away from heavy pollution sources, such as smelteries, coal mines, and thermal power plants, 2 km away from medium pollution sources, such as chemical, rubber, and galvanization industries, and 1 km away from light pollution sources, such as packing houses, tanneries, and boiler rooms.