Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Electrical Specifications

Electrical Specifications

Table 5-2  Electrical Specifications

Item

Specifications

AC input

AC input system

110 V AC dual-live wire

AC input voltage

85 V AC-300 V AC

Input frequency

Frequency range: 45-66 Hz; nominal frequency: 50 Hz or 60 Hz

Power factor

≥ 0.99 (rated input and load)

Total harmonic distortion (THD)

≤ 5% (Vin = 208 V AC, 220 V AC, 230 V AC, 50%-100% load)

DC output

Output voltage range

-42 V DC to -58 V DC

Default output voltage

-53.5 V DC

Output power

The maximum output power is the number of rectifiers multiplied by the output power of a single rectifier.

Regulated voltage precision

≤ ±1%

Ripple and noise

≤ 200 mVp-p

Noise weighting

≤ 2 mV

Imbalance of load sharing

< ±5% (20%-100% load percentage)

AC input protection

AC input overvoltage protection threshold

> 300 V AC

AC input overvoltage recovery threshold

When the voltage is restored to 290 V AC, the output resumes.

AC input undervoltage protection threshold

< 85 V AC

AC input undervoltage recovery threshold

When the voltage is restored to 90 V AC, the output resumes.

DC output protection

DC output overvoltage protection threshold

Range: -58.5 V DC to -60.5 V DC

  1. If an overvoltage occurs inside a rectifier, the rectifier locks out.
  2. If the external voltage is above –63 V for more than 500 ms, the rectifier locks out.

AC surge protection

Level B surge protection; nominal surge discharge current: 30 kA (8/20 µs); maximum surge discharge current: 60 kA (8/20 µs)

DC surge protection

Differential mode: 10 kA (8/20 µs); common mode: 20 kA (8/20 µs)

Safety and regulatory design

Complies with the IEC/EN60950-1.

MTBF

200,000 hours