Product Description 15

OceanStor 5300 V3, 5500 V3, 5600 V3, 5800 V3, and 6800 V3 Storage System V300R003

This document introduces the storage system from the aspects of the market position, features, architecture, technical specifications, production configuration, environment requirement, standard compliance, and granted certifications.
Rate and give feedback :
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Temperature, Humidity, and Altitude

Temperature, Humidity, and Altitude

Temperature, humidity, and altitude requirements must be met so that storage systems can correctly work or be properly preserved.

Table 7-1 lists the temperature, humidity, and altitude requirements of the storage systems.

Table 7-1  Temperature, humidity, and altitude requirements of the storage systems

Parameter

Condition

Requirement

Temperature

Operating temperature

  • 5°C to 40°C (41°F to 104°F) when the altitude is between -60 m and +1800 m (-196.85 ft. and +5905.51 ft.)
  • At altitudes between 1800 m and 3000 m (5905.51 ft. and 9842.52 ft.), the temperature drops by 1°C (1.8°F) for 220 m (721.78 ft.) of altitude increase.

Operating temperature change rate

1°C (1.8°F)/minute

Non-operating ambient temperature

-40°C to +70°C (-40°F to +158°F)

Storage temperature (during transportation and storage with packages)

-40°C to +70°C (-40°F to +158°F)

Humidity

Operating humidity

10% RHa to 90% RH

Non-operating humidity

5% RH to 95% RH

Maximum humidity change rate

10%/hour

Storage humidity (during transportation and storage with packages)

5% RH to 95% RH

Altitude

Operating altitude of disks

-304.8 m to +3048 m (-999.99 ft. to +9999.99 ft.)

Non-operating altitude of disks

-305 m to +12192 m (-1000.64 ft. to +39999.51 ft.)

a: RH, Relative Humidity