Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
ALM-23000001 The Middle of the I/O Module Air Inlet Temperature Reaching the Overtemperature Threshold

ALM-23000001 The Middle of the I/O Module Air Inlet Temperature Reaching the Overtemperature Threshold

Description

Alarm message:

Middle of the I/O board (xxx) air inlet temperature (xx degree C) reaches the overtemperature threshold (xx degree C).

Attribute

Alarm ID

Alarm Severity

Auto Clear

23000001

Minor

Yes

Parameters

Name

Meaning

Alarm Severity

Indicates the alarm severity.

Alarm Source

Indicates the alarm source.

Subject

Indicates the event body for which an alarm is generated.

Time

Indicates the time when an alarm is generated.

Description

Provides an alarm description.

Event Code

Indicates the event code of an alarm.

Impact on the System

The PCIe cards on the front I/O module (FIO) operate unstably. If the alarm persists, services related to the PCIe cards may be interrupted.

Possible Causes

  • The ambient temperature is higher than 30°C (86°F).
  • The air intake vent is blocked.
  • The upper threshold for minor alarms is not properly set for the sensor.
  • The FIO is faulty.

Procedure

  1. Check that the air conditioners in the equipment room are working properly. Reduce the ambient temperature for the server or move the server to a place at a lower temperature. Ensure that the ambient temperature is in the range of 10°C to 30°C (50°F to 86°F). Then check whether the alarm is cleared automatically.

    • If yes, no further action is required.
    • If no, go to Step 2.

  2. Check whether the air intake vent is blocked.

  3. Remove barriers from the air intake vent. Then check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 4.

  4. Run the smmget -l bladeN -t sensorname -d thresholdall command on the CMC CLI, and check whether the upper threshold for minor alarms is set properly.

    The proper threshold for the sensor is as follows:

    FioInlet M Temp: 48°C

    If the command output is as follows, the threshold is set properly:

    root@SMM:/#smmget -l blade2 -t FioInlet M Temp -d thresholdall     
    Upper Non-recoverable:  Not supported.  
    Upper Critical       :  Not supported.  
    Upper Non-critical : 48.000 Celsius  
    Lower Non-critical : Not supported.  
    Lower Critical       : Not supported.  
    Lower Non-recoverable: Not supported.     

  5. Run the smmset -l bladeN -t sensor -d uppernoncritical -v value command (value indicates the upper threshold for minor alarms) on the CMC CLI to change the threshold. Then check whether the alarm is cleared.

  6. Replace the FIO. Five minutes later, check whether the alarm is cleared.

    For details about how to replace an FIO, see the KunLun 90xx V100R001 User Guide.

    • If yes, no further action is required.
    • If no, go to Step 7.

  7. Contact Huawei technical support.