CLOCK/4/FREQ_INSTANT_CHG
Description
The number of frequency changes is not 0. The log records the latest change and number of frequency changes.
Parameters
Parameter Name | Parameter Meaning |
---|---|
[LONG] |
Indicates the latest frequency after change. |
[ULONG] |
Indicates the counter of frequency change. |
Procedure
- If the clock source is switched, this is a normal situation.
- If the clock source of the upstream device is switched, this is a normal situation.
- Run the display clock { bits0 | bits1 } command to view the BITS interface configuration. Check whether the clock configurations of upstream and downstream devices are correct, for example, whether bit/hz in the output mode of the upstream device is the same as that in the input mode of the local device.
- Check the frequent offset of the upstream clock source. Tools may be required.
- After the clock source is switched, if the log is generated on all interfaces of the local device, the local clock board may be faulty. Then perform an active/standby switchover on the clock boards.
- Record this log message and contact technical support personnel.