ALM-0x02000017 Failed to Read Hard Disk Temperature (Disk, Minor Alarm)
Description
Alarm message:
Failed to obtain data of the [arg1] disk arg2 temperature (SN: arg3, BN: arg4).
From iBMC V316, the CPU and disk alarms will also include the SN and BOM code and the mainboard and memory alarms will also include the BOM code.
This alarm is generated when the system failed to obtain the disk temperature.
Alarm object: Disk
Attribute
Alarm ID |
Alarm Severity |
Auto Clear |
---|---|---|
0x02000017 |
Minor |
Yes |
Parameters
Name | Meaning |
---|---|
arg1 |
Location of the hard disk. For example, FM or CMn. |
arg2 |
Slot number of the hard disk. |
arg3 |
Disk serial number. |
arg4 |
BOM code. |
Impact on the System
The temperature cannot be monitored. No alarm will be reported when the temperature is not in the normal range.
Possible Causes
- The channel in which the iBMC accesses the drive is abnormal.
- The hard drive is faulty.
- The drive backplane is faulty.
Procedure
- Restart the iBMC. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 2.
- Remove the power cable to power off the server, and then reconnect the power cable to power on the server. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 3.
- Reconnect the cable to the drive backplane holding the sensor. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 4.
- Replace the hard disk. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 5.
- Replace the drive backplane holding the sensor. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 6.
- Contact technical support.