ALM-0x12000017 Failed to Read Outlet Temperature (Chassis, Minor Alarm)
Description
Alarm message:
Failed to obtain data of the air outlet arg1 temperature.
This alarm is generated when the system failed to obtain the outlet temperature.
Alarm object: chassis
Impact on the System
The temperature at the air outlet cannot be monitored, and the fan speed adjustment is affected.
Procedure
- Log in to the iBMC WebUI or CLI.
For details, see the iBMC user guide of the server you use.
- Restart the iBMC.
- On the WebUI, choose Restart iBMC. and click
- On the CLI, run the ipmcset -d reset command.
- After the iBMC restarts, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 4.
- Remove and reinstall the server node. Check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 5.
- Replace the component holding the outlet sensor. Then, check whether the alarm is cleared.
For details, see "Replacing Parts" in the user guide.
The air outlet temperature sensor of the high-density server is on the mainboard.
If yes, no further action is required.
If no, go to 6.
- Contact technical support engineer.