ALM-0x0100003D Memory Overtemperature (Memory, Major Alarm)
Description
Alarm message:
The memory (arg1 arg2) temperature (arg3 degrees C) exceeds the overtemperature threshold (arg4 degrees C)(SN: arg5, BN: arg6).
This alarm is generated when the memory temperature exceeds the overtemperature major threshold.
Alarm object: memory
Parameters
Name | Meaning |
---|---|
arg1 |
Socket No. of the CPU. |
arg2 |
DIMM silkscreen, for example, DIMM000. |
arg3 |
Current reading of the sensor. |
arg4 |
Alarm threshold. |
arg5 |
Disk serial number. |
arg6 |
BOM code. |
Possible Causes
A fan module is faulty.
The equipment room temperature exceeds the normal range.
The air inlet or outlet is blocked.
- Idle slots or spaces are not installed with filler panels.
The DIMM is faulty.
Procedure
- Check whether there is fan alarm generated.
- Replace the fan module. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 3.
- Check whether the equipment room temperature exceeds the normal range.
- Reduce the equipment room temperature to the normal range. After 5 minutes, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 5.
- Check whether the server air inlet and outlet are blocked.
- Clear the blockage. After 5 minutes, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 7.
- Check whether there are empty slots in the server.
- Install filler panels in empty slots. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 9.
- Replace the DIMM. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 10.
- Contact technical support engineer.