ALM-0x1200001F M.2 Slot Zone Overtemperature (Chassis, Minor Alarm)
Description
Alarm message:
The temperature (arg1degrees C) of the M.2 slot zone on the mainboard exceeds the overtemperature threshold (arg2degrees C).
This alarm is generated when the M.2 slot zone temperature on the mainboard exceeds the overtemperature threshold. This alarm is cleared when the temperature is within the normal range.
Alarm object: chassis
Possible Causes
The equipment room temperature exceeds the normal range.
The air inlet or outlet is blocked.
Filler panels are not installed in empty slots.
The device holding the air inlet sensor is faulty.
Procedure
- Check whether there is fan alarm generated.
- Replace the fan module. After 5 minutes, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 3.
- Check whether the equipment room temperature exceeds the normal range.
- Reduce the equipment room temperature to the normal range. After 5 minutes, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 5.
- Check whether the server air inlet and outlet are blocked.
- Clear the blockage. After 5 minutes, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 7.
- Replace the M.2 SSD card. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 8
- Contact technical support engineer.