ALM-0x2C000007 Server Powered Off (System, Major Alarm)
Description
Alarm message:
The [arg1] power arg2 failure results abnormal power-off.
This alarm is generated when a voltage sag or an unexpected power failure occurs on the mainboard.
Alarm object: system
Parameters
Name | Meaning |
---|---|
arg1 |
Serial number of the power supply, for example, LPM1. |
arg2 |
Power supply subsystem name. For example, STBY_5V0 or STBY_1V8_PCH. |
Procedure
- Check whether the power supplies in the equipment room are sufficient for server operation.
- Ensure sufficient power supplies for server operation. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 3.
- Power off the server (by removing the power cable or server node) and then power on the server (by reconnecting the power cable or reinstalling the server node). Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 4.
- Replace the power cable. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 5.
- Replace the power supply unit (PSU). Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 6.
- Replace the power supply backplane. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 7.
- Replace the mainboard. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 8.
- Contact technical support engineer.