(Optional) Connecting the Humidifier Water Inlet Pipe
Context
(1) Connector with inner screw threads: G 1/2 inch, delivered with the water inlet pipe for the smart cooling product |
(2) Rigid pipe conversion adapter: G 1/2 inch; connected to a rigid pipe with outer screw threads |
(3) Rigid pipe: made of PP-R or other materials |
(4) Pagoda connector: G 1/2 inch; connected to a pagoda connector with outer screw threads |
(5) Hose clamp |
(6) Hose: made of EPDM or other materials |
Bottom Pipe Routing
- Straighten the water inlet pipe delivered with the smart cooling product, and route it from the inside to the outside through the
water inlet hole at the bottom of the smart cooling product.
Figure 3-36 Downward routing of the water inlet pipe
The other end is a reserved G 1/2 inch connector with inner screw threads. Connect the other end to a hose or rigid pipe based on site requirements.
- Clean the engineering pipes before connecting the water inlet pipe to the engineer pipe to avoid impurities entering into the humidifier.
- Connect the water inlet pipe to the engineer pipe and wrap the pipe with thermal insulation foam.
Top Pipe Routing
When routing pipes from the top, do not route the pipes over servers or other devices to protect them from being affected by pipe leaks.
- Straighten the water inlet pipe delivered with the smart cooling product, and route it from the inside to the outside through the
water inlet hole on the top of the smart cooling product.
Figure 3-37 Upward routing of the water inlet pipe
- The other end is a reserved G 1/2 inch connector with inner screw threads. Connect the other end to a hose or rigid pipe based on site requirements.
- Secure the water inlet pipe inside the cabinet to the left post of the cabinet using cable ties.
- Clean the engineering pipes before connecting the water inlet pipe to the engineer pipe to avoid impurities entering into the humidifier.
- Connect the water inlet pipe to the engineer pipe and wrap the pipe with thermal insulation foam.