Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Connecting DC Power Cables

Connecting DC Power Cables

When a DC power supply is used to supply power for the storage system, connect the DC power cables correctly before powering on the device.

Prerequisites

The storage system is disconnected from the external power supply.

The required installation tools and materials include:

  • DC power cables
  • Diagonal pliers
  • Phillips screwdriver

Context

  • To ensure power reliability, you need to connect the power cables in two sides of the storage system to two independent power supplies. When one fails, the other can supply power.
  • The input DC voltage ranges from -48 V to -60 V.
  • Using DC power prolongs the service life of devices to some extent. In many equipment rooms, DC power is regarded as standard.

Procedure

  1. Connect the DC power cables of the controller enclosure.

    NOTE:

    Figure 6-78 shows the 2 U controller enclosure connecting the DC power cable, and Figure 6-79 shows the 3 U/6 U controller enclosure connecting the DC power cable.

    1. Remove the plastic insulation tubes on the OT terminals of the DC power cables with the diagonal pliers.
    2. Remove the protective cover on the DC power module, as shown in step 1 of Figure 6-78.
      Figure 6-78 Connecting the DC power cable of the 2 U controller enclosure

      Figure 6-79 Connecting the DC power cable of the 3 U/6 U controller enclosure

    3. Unfasten the screws of the DC power cable with the Phillips screwdriver, put the screws through the shock absorption sheets, washers, and OT terminal round holes, and then fasten the screws that attach the power module, as shown in step 2 of Figure 6-78.
      NOTE:
      • When unfastening the screws from the DC power cable, prevent the shock absorption sheets and washers from sliding off.
      • Connect the OT terminal of the black cable to the RTN (+) end, and the OT terminal of the blue cable to the NEG (-) end. (The colors of DC power cables that connect to the anode and cathode of the DC power supply are subject to the colors of the DC power cables actually configured in users' equipment rooms.)
    4. Install the protective cover on the DC power module, as shown in step 3 of Figure 6-78.

  2. Repeat Step 1.1 to Step 1.4 to connect the DC power supply to disk enclosures.
  3. Check whether the DC power cables of the controller enclosure and disk enclosures are correctly connected to the DC power supply. Figure 6-80, Figure 6-81, and Figure 6-82 show how to connect a controller enclosure and an ordinary disk enclosure using DC power cables.

    Figure 6-80 Complete view of the connected DC power cables (2 U controller enclosure)

    Figure 6-81 Complete view of the connected DC power cables (3 U controller enclosure)

    Figure 6-82 Complete view of the connected DC power cables (6 U controller enclosure)

  4. Route and bind DC power cables.

    NOTE:

    For routing and bundling principles, see General Cable Routing Principles and Cable Routing and Bundling Basics.

Translation
Download
Updated: 2019-07-11

Document ID: EDOC1000181531

Views: 101147

Downloads: 953

Average rating:
This Document Applies to these Products
Related Documents
Related Version
Share
Previous Next