Port Settings
Setting DO Parameters
The SmartLogger provides three DO ports, which support external router reset and the audible and visual alarm for grounding faults.
Connecting a 3G Router over the DO Port
Considering the restrictions on the current that can pass through the DO port of the SmartLogger, you need to determine the number of DO ports to be used for the control based on the maximum power supply current of the 3G router (the maximum power supply current can be calculated based on the maximum power consumption and DC power supply voltage).
- When the power supply current is smaller than 1 A, use one DO port.
- When the power supply current is larger than 1 A but smaller than 1.6 A, use two DO ports.
- When the power supply current is larger than 1.6 A but smaller than 2.4 A, use three DO ports.
- When the power supply current is larger than 2.4 A, access is not allowed because the current exceeds the upper limit.
Connect one DC power cable of the 3G router to one of the DO ports, power on or off the wireless module by connecting or disconnecting the DO dry contact to control the reset of the 3G router.
Log in as Advanced User. Choose , and set the corresponding DO port to Reset the external router.
Connecting the Horn Strobe over the DO Port
Connect one DC power cable of the horn strobe to one of the DO ports, and power on or off the horn strobe by connecting or disconnecting the DO dry contact to achieve the audible and visual alarm for grounding faults.
Log in as Advanced User. Choose , and set the corresponding DO port to Ground fault audit and vis alm.
Setting USB Parameters
This topic describes how to set USB parameters for resetting an external 3G router over the WebUI.
Context
- Only the SmartLoggers in versions later than V100R001C90SPC300 enjoy this function.
- If the maximum working current of the 3G router is greater than 1 A, it cannot be connected over a USB port.
Connecting a 3G Router over a USB
USB configuration
After connecting the 3G router to the SmartLogger properly, you can set USB parameters over the WebUI to make the external 3G router automatically reset if the SmartLogger fails to connect to the management system, email server, or FTP server within 30 minutes.